Plan Review Notes
Plan Review Notes For Permit 21050038
Permit Number 21050038
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-05-04 16:42:33.00000CONDUCTORS BETWEEN COMBINER PANEL AND PV DISCONNECT,
 AND BETWEEN PV DISCONNECT AND SUPPLY SIDE TAP, MUST
 HAVE A MINIMUM AMPACITY OF 104 @ 75 DEGREES C. USE
 MINIMUM #2 THWN COPPER.
2021-05-03 15:30:05.00000DROPPED OFF