Date Text
2021-10-26 15:17:29.00000SHEET PV-06: "120 AMP" PV OVERCURRENT PROTECTIVE DEVICE
 IS NOT A STANDARD NEC SIZE, SEE TABLE 240.6 (A). #3
 CONDUCTORS BETWEEN COMBINER PANEL AND SUPPLY-SIDE TAP
 DO NOT HAVE SUFFICIENT AMPACITY FOR THIS SYSTEM.
 MINIMUM CONDUCTOR AMPACITY = 111 AMPS; USE 75 DEGREE
 COLUMN OF TABLE 310.15 (B)(16). SEE 110.14 (C)(1).
2021-10-26 13:57:04.00000REVISION EMAILED IN 1:56 PM, 10/26/21,
 PERMITTING@MERAKISOLUTIONS.COM