Plan Review Notes
Plan Review Notes For Permit 21040876
Permit Number 21040876
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-05-04 15:44:36.00000CONDITIONAL APPROVAL: REFER TO SHEET PV-2. PV
 DISCONNECT MUST CONTAIN 45A FUSES, NOT 40A. SYSTEM
 INCORPORATES (33) IQ7-60 INVERTERS @ 1 AMP EACH. 33 X 1
 X 1.25 = 41.25 MINIMUM REQUIRED AMPACITY.