Plan Review Notes For Permit 21040805
Permit Number 21040805
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-06-24 09:02:47.00000 
 PLAN REVIEW #:21040805
  
 PROJECT: FLORIDA JOINT AND SPINE
  
 LOCATION: 5115 US 27 N SEBRING
  
 OCCUPANCY: BUSINESS
  
 REVIEWED BY: FIRE MARSHAL MICHAEL RODDE
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 ______________________________
 PLANS WERE REVIEWED BEFORE THE SITE PLAN FOR THE
 BUILDING HAS BEEN APPROVED. THE COMMENTS MADE AT THIS
 TIME ON THE CURRENT PLANS ARE ONLY PRELIMINARY AND
 STILL SUBJECTED TO A FULL PLAN REVIEW AND ADDITIONAL
 COMMENTS BASED ON THE SITE PLANS APPROVAL. AT THIS
 TIME, PLANS ARE NOT APPROVED BASED ON COMMENTS BELOW
 AND FULL REVISIONS WILL BE REQUIRED. IN SUBMITTING
 REVISIONS, ENSURE A LETTER IS PROVIDED RESPONDING TO
 THE CHANGES AND THE CHANGES WITHIN THE PLANS ARE
 CLOUDED.
 1. ENSURE ADDRESS IS LOCATED ON BUILDING AT MAIN
 ENTRANCE. MINIMUM 6-INCH NUMBERS REQUIRED.
 2. SAFEGUARDS FOR CONSTRUCTION SHALL BE IN PLACE IN
 ACCORDANCE WITH NFPA 1 AND NFPA 241, STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS. ENSURE CERTIFIED FIRE EXTINGUISHERS ARE
 PROPERLY LOCATED THROUGHOUT BUILDING DURING
 CONSTRUCTION AND NO SMOKING TAKES PLACE INSIDE THE
 BUILDING. NFPA 1: 16.1.1
 3. MISSING EXTINGUISHER ON THE SECOND FLOOR AND PROVIDE
 SIZE OF EXTINGUISHER. THIS SHALL BE BASED ON THE
 OCCUPANCY TYPE AND USE OF THE BUILDING IN ACCORDANCE
 WITH NFPA 10.
 4. KNOX BOX IS REQUIRED FOR THE BUILDING
 5. MISSING STAIR DETAILS
 6. MISSING DOOR SCHEDULE AND HARDWARE
 7. EXIT AND EMERGENCY LIGHTS DO NOT MATCH ON ANY PAGE
 8. ALL ROOMS SHALL HAVE PROPER SIGNAGE FOR
 IDENTIFICATION
 9. PROVIDE PLACARDS OUTSIDE OF ROOMS INDICATING ANY
 POTENTIAL HAZARD. TYPICAL SIGNAGE IS WHITE LETTERING ON
 RED BACKGROUND.
 10. WATER SUPPLY SHALL BE ESTABLISHED ON SITE PRIOR TO
 ANY COMBUSTIBLES BEING BROUGHT ONTO THE SITE. FURTHER
 EMERGENCY ACCESS SHALL; BE PROVIDED TO THE SITE. THIS
 ACCESS SHALL BE MAINTAINED AND SUPPORT WEIGHT OF
 EMERGENCY APPARATUS.
 11. ALL EGRESS SHALL HAVE PANIC HARDWARE.
 12. PROVIDE UL DETAILS FOR MECHANICAL PENETRATIONS
  
  
  
  
 13. PROVIDE DETAIL SHEETS FOR THE INTERIOR FINISHES,
 CONTENTS AND FURNISHINGS
 14. NO STORAGE MAY BE LOCATED WITHIN 36 INCHES OF ANY
 ELECTRICAL PANELS. STRIPE THIS AREA WITH YELLOW
 DIAGONAL LINES TO INDICATE A NO STORAGE ZONE.
 15. MISSING DETAIL OF THE ROOF OPENING.
 16. WHERE ROOF ACCESS IS, THIS AREA SHALL BE STRIPED
 WITH YELLOW DIAGONAL LINES AS A NO STORAGE AREA
 17. TAMPERS WILL BE REQUIRED ON BACKFLOW AND BE TIED TO
 THE FIRE ALARM SYSTEM.
 18. FIRE RISER ROOM IS INCORRECT AND NOT RATED PROPERLY
 19. SEPARATE PLANS/PERMIT WILL BE REQUIRED FOR THE
 PORTION OF THE UNDERGROUND RELATED TO THE FIRE
 SPRINKLER SYSTEM (BACKFLOW TO BUILDING).
 20. MECHANICAL SMOKE DETECTORS ARE NOT CLEARLY DEPICTED
 ON THE PLANS, SHALL CLOUD AREAS
  
  
 ALL LIFE SAFETY FEATURES SHALL BE VERIFIED DURING
 CONSTRUCTION BY THE FIRE MARSHAL’S OFFICE.
  
 TO SCHEDULE AN INSPECTION, YOU MUST CALL THE FIRE
 MARSHAL’S OFFICE AT 863-402-7665 24 HOURS IN ADVANCE
 FOR AN APPOINTMENT.
  
  
 REVIEW FEE – $1600
  
 ... PLEASE BE ADVISED THIS REVIEW OF PLANS SUBMITTED IS
 A CURSORY REVIEW TO ASSIST THE CONTRACTOR IN COMPLIANCE
 WITH APPLICABLE FIRE SAFETY CODES. THIS REVIEW IS NOT
 INTENDED TO BE A FINAL APPROVAL OF THE SUBMITTED PLANS.
 IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE
 THAT THE PLANS ARE IN COMPLETE COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES SLATE S1ATUTES AND LOCAL
 ORDINANCE. IN THE EVENT THAT FURTHER EXAMINATION OR
 SITE INSPECTION REVEALS AREAS OF NON-COMPLIANCE. IT
 SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILI1Y, AT THEIR
 SOLE EXPENSE TO BRING THOSE AREAS IN COMPLIANCE. FIRE
 MARSHAL’S OFFICE ASSUMES NO RESPONSIBILITY FOR THE
 CONTRACTOR'S FAILURE TO BE IN COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES, STATE STATUTES AND LOCAL
 ORDINANCES.
  
  