Date Text
2021-04-27 15:58:30.000001] PROVIDE SOLAR APPLICATION, NOT RESIDENTIAL BUILDING
 APPLICATION.
 2] SHEET E-1: IQ7-72-2-US MICROINVERTERS HAVE A MAXIMUM
 CONTINUOUS OUTPUT CURRENT OF 1.21 AMPS @ 240 VOLTS.
 REVISE ONE-LINE AND ALL NOTES TO REFLECT THE COMBINED
 INVERTER CURRENT OUTPUT. ASSUMING THE USE OF THESE
 MICROINVERTERS, MINIMUM FUSING SHOULD BE 45 AMPS (27 X
 1.21 X 1.25, NEXT SIZE O/C PROTECTION) AND RATED OUTPUT
 AC CURRENT LABEL SHOULD SHOW 33 AMPS. IN ANY CASE,
 COMBINED INVERTER OUTPUTS, LABELING, CONDUCTOR SIZES,
 AND OVERCURRENT PROTECTION MUST BE CONSISTENT.
2021-04-27 09:54:21.00000PERMIT PACKAGE MAILED IN. . FILLED OUT WRONG PERMIT
 APP, FILLED OUT RESIDENTIAL APP, EMAILED THE COMPANY
 THE SOLAR APP TO FILL OUT, HAVE NOT RECEIVED IT.