Date Text
2021-04-23 14:53:02.00000ONE-LINE DIAGRAM: IF USING LINE-SIDE TAP, GROUNDED
 CONDUCTOR BETWEEN PV DISCONNECT AND TAP MUST BE MINIMUM
 #8 CU. SEE TABLE 250.102 (C)(1).
2021-04-22 09:03:43.00000DROPPED OFF