Plan Review Notes
Plan Review Notes For Permit 21040619
Permit Number 21040619
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-04-23 13:41:24.000001] SHEET PV 4: #8 CU NOT APPROVED BETWEEN INVERTER AND
 PV DISCONNECT; MINIMUM CONDUCTOR AMPACITY @ 75 DEGREES
 C = 52.5 AMPS. USE MIN #6 CU.
 2] SPEC SHEET FOR MODULES DOES NOT MATCH MODULE
 SPECIFIED ON PLANS.
2021-04-21 10:17:47.00000EMAILED IN BY KHADLEY@FREEDOMFOREVER.COM