Plan Review Notes
Plan Review Notes For Permit 21040273
Permit Number 21040273
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2021-04-19 08:49:19.000001] CONDUCTORS BETWEEN COMBINER PANEL AND SERVICE MUST
 BE MINIMUM #8 CU. 310.15 (B)(16), 75 DEGREE COLUMN FOR
 #10 = 35 AMPS. MINIMUM AMPACITY REQUIRED FOR THIS
 SYSTEM IS 36.25. SEE ALSO 240.4 (D)(7), REFERENCING
 240.4 (G).
 2] CHANGE GROUNDED CONDUCTOR BETWEEN SUPPLY-SIDE TAP
 AND PV DISCONNECT TO MINIMUM #8 CU. TABLE 250.102
 (C)(1).