2021-04-14 13:54:37.0000004/13/2021 ELECTRICAL SHEET, REVISION 1:
 1] QUANTITY OF MODULES SHOWN ON ONE LINE DIAGRAM DOES
 NOT MATCH QUANTITY SHOWN ON PAGE SUMMARY (TOP CENTER OF
 SHEET)
 2] THE GROUNDED CONDUCTOR BETWEEN THE SERVICE AND THE
 PV DISCONNECT MUST BE MINIMUM #8 CU IF USING A
 SUPPLY SIDE TAP. SEE TABLE 250.102 (C)(1) FOR MINIMUM
 SIZE OF SUPPLY SIDE BONDING AND GROUNDED CONDUCTORS.
  