Plan Review Notes For Permit 21040018
Permit Number 21040018
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-04-01 16:28:14.00000SHEET E-1: #10 THWN-2 CONDUCTORS FROM SUPPLY SIDE TAP
 TO PV DISCONNECT, AND FROM PV DISCONNECT TO COMBINER,
 CANNOT BE PROTECTED AT 40 AMPS; EXCEEDS TEMPERATURE
 RATING OF TERMINALS, SEE 110.14 (C)(1) AND TABLE 310.15
 (B)(16). USE 30A MAXIMUM OVERCURRENT PROTECTION OR
 INCREASE CONDUCTOR SIZE.