Plan Review Notes
Plan Review Notes For Permit 21030904
Permit Number 21030904
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-03-25 14:24:44.000001] #6 THWN-2 CONDUCTORS BETWEEN COMBINER PANEL AND
 SERVICE ARE UNDERSIZED FOR 125% OF COMBINED INVERTER
 OUTPUTS. REPLACE WITH MINIMUM #4.
 2] INCLUDE RAPID SHUTDOWN GRAPHIC LABEL IDENTIFIED IN
 690.56.
 3] INCLUDED RAPID SHUTDOWN SWITCH IDENTIFICATION LABEL
 PER 690.56.