Plan Review Notes For Permit 21030594
Permit Number 21030594
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2021-04-07 16:31:22.000001] PROVIDE SPECIFICATION SHEET(S) FOR TESLA GATEWAY
 2] ONE-LINE DIAGRAM IS UNCLEAR: #2 CONDUCTORS TO 40A
 BACKFED PV BREAKER? 200A SUBPANEL RATED FOR 125A?
 OVERCURRENT PROTECTION FOR EXISTING SUBPANEL?
 3] #8 CU EQUIPMENT GROUNDING CONDUCTOR POSSIBLY TOO
 SMALL TO BE USED WITH #2 CU UNGROUNDED CONDUCTORS; WILL
 BE DETERMINED BY CIRCUIT OVERCURRENT PROTECTION.