Plan Review Notes
Plan Review Notes For Permit 21020833
Permit Number 21020833
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-02-25 15:43:48.000001] LABEL IDENTIFICATION SHEET MUST SHOW RAPID SHUTDOWN
 COMPLIANCE LABEL WITH GRAPHIC PER 690.56.
 2] LABEL IDENTIFICATION SHEET MUST SHOW RAPID SHUTDOWN
 SWITCH LABEL TO BE PLACED ON OR WITHIN 3 FEET OF PV
 DISCONNECT
 3] ONE-LINE DIAGRAM SHOWS PV DISCONNECT AS 40 AMP, WITH
 50 AMP FUSES. PLEASE CORRECT.