Plan Review Notes
Plan Review Notes For Permit 21020832
Permit Number 21020832
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-02-25 15:55:38.000001] PROVIDE COMPLETE LABEL IDENTIFICATION SHEET SHOWING
 ALL REQUIRED LABELING PER ARTICLES 690 & 705.
 2] ONE-LINE DIAGRAM SHOWS PV DISCONNECT AS 40 AMP, WITH
 50 AMP FUSES. PLEASE CORRECT.