Plan Review Notes
Plan Review Notes For Permit 20120701
Permit Number 20120701
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-12-29 16:04:51.000001] SHEETS A-1, A-2, AND A-3 MUST SHOW COMPLIANCE WITH
 FLORIDA FIRE PREVENTION CODE 11.12.2.2.2. MINIMUM THREE
 FOOT SEPARATION FROM ROOF RIDGE APPLIES.
 2] PROVIDE SPECIFICATION PAGE(S) FOR ENPHASE AC
 COMBINER PANEL.
 3] SHEET E-4 MUST SHOW NEUTRAL-TO-CASE BOND IN PV
 DISCONNECT FOR SUPPLY-SIDE PV CONNECTION. THE SEPARATE
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN THE PV DISCONNECT
 AND THE SUPPLY-SIDE TAP SHOULD BE REMOVED.
 EMAILED THIS REPORT TO CONTRACTOR'S EMAIL-OF-RECORD
 12/29/20; WAS RETURNED AS UNDELIVERABLE.
  