Date Text
2020-12-04 15:16:58.000001] PV DISCONNECT RATING MUST BE NOT LESS THAN 125 % OF
 COMBINED INVERTER OUTPUT
 2] SHOW RATINGS OF OVERCURRENT DEVICES IN COMBINER
 PANEL; MUST BE NOT LESS THAN 125% OF INVERTER OUTPUT
 3] PROVIDE PE SEAL FOR PROPOSED GROUND-MOUNT DESIGN,
 REFERENCING COMPLIANCE WITH 6TH EDITION FLORIDA
 BUILDING CODE