Plan Review Notes
Plan Review Notes For Permit 20110512
Permit Number 20110512
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-08 13:48:12.00000GAVE BACK TO CONTRACTOR 12/08/20
2020-11-30 12:21:10.00000I HAVE RECEIVED AND REVIEWED A ONE PAGE PLAN FOR WHAT
 WAS SENT TO BE FOR FIRE UNDERGROUND, HOWEVER, PLAN
 APPEARS TO BE UTILITIES PAGE FROM A FINAL SITE PLAN.
 PLAN IS UNABLE TO REVIEW AS IT IS INCONCLUSIVE FOR THE
 REASONS STATED BELOW. RESUBMIT PLAN WITH MORE DETAIL,
 DESCRIPTION, AND INFORMATION. ANY QUESTIONS, THIS
 AUTHORITY MAY BE CONTACTED THROUGH ABOVE EMAIL OR
 TELEPHONE NUMBER.
  
  
 1. IF PLAN IS FOR UNDERGROUND FOR FIRE SPRINKLER
 SYSTEM, PLAN SHALL BE SUBMITTED BY INSTALLING
 CONTRACTOR SHOWING POC AND INCOMING LINE FEEDING FIRE
 RISER AND THEN OUTGOING LINE FEEDING FDC. PIPE SIZE,
 TYPE, MAKE SHOULD ALL BE CALLED OUT. THERE SHOULD BE
 RESTRAINING DETAILS, SPEC/MATERIAL PACKET, ETC…THE
 ENTIRE BUILDING SHOULD BE ON A SINGLE PAGE. CONTRACTOR
 WILL ALSO NEED TO SUBMIT STATE OF FLORIDA LICENSE TO
 INSTALL.
 2. IF PLAN IS A REVISED SITE FINAL, PLAN IS STILL
 INCONCLUSIVE. AGAIN, THERE SHOULD BE RESTRAINING
 DETAILS, DETAILS FOR INTERSECTING PIPE, FULL BUILDING
 ON SITE, ETC…
 3. IF FINAL SITE PLAN WAS ALREADY APPROVED AND THIS IS
 ONLY FOR THE INSTALLATION OF HYDRANTS AND ASSOCIATED
 WATER MAINS FOR HYDRANTS, NO PERMIT IS REQUIRED TO
 INSTALLED AS THIS WORK IS PART OF THE ACTUAL SITE.
  
  
  
  
 KERRY BARNETT
 ___________________________________
 KERRY BARNETT, FIRE SAFETY INSPECTOR & PLANS EXAMINER
 *3RD PARTY REVIEWER FOR HIGHLANDS COUNTY AS ALLOWED PER
 F.S.633
  