-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 20100030
Permit Number 20100030
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-10-02 09:27:23.00000FSEC CERTIFICATION AND TITLE ON ONE-LINE DIAGRAM
 INDICATE IQ7 INVERTERS; MICROINVERTER SPECIFICATION ON
 ONE-LINE SHOWS CURRENT PARAMETER FOR IQ7+ INVERTER
 (1.21 AMPS).
 MICROINVERTER SPEC SHEETS ATTACHED DO NOT MATCH DATA ON
 DRAWINGS OR FSEC CERTIFICATION.
 PLEASE CLARIFY EXACTLY WHICH COMPONENT IS PROPOSED;
 INVERTER DATA MUST BE CONSISTENT THROUGHOUT PLAN.
  
 AC CURRENT OUTPUT LABEL MUST EXACTLY MATCH TOTAL SYSTEM
 OUTPUT WITHOUT ANY DEMAND ADJUSTMENTS.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved