Plan Review Notes For Permit 20100019
Permit Number 20100019
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-10-01 15:16:19.00000RISER DIAGRAM: NEUTRAL CONDUCTOR MUST BE EXTENDED TO
 TRANSFER SWITCH (INSTALLED WITH UNGROUNDED CONDUCTORS)
 FOR BOTH SERVICE CONDUCTORS AND FEEDERS. SHOW
 NEUTRAL/GROUND BOND IN TRANSFER SWITCH. PROVIDE
 SPECIFICATION SHEET FOR TRANSFER SWITCH; MUST BE LISTED
 AS SERVICE-RATED.