Date Text
2020-09-30 08:41:04.00000SHEETS A-00 & S-01: ROOF LAYOUT DOES NOT COMPLY WITH
 FLORIDA FIRE PREVENTION CODE11.12.2.2.2. SHOW MINIMUM 3
 FOOT SEPARATION BETWEEN MODULES AND ROOF RIDGE.
 SHEET E-01: EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT IS TOO SMALL FOR 80A
 OCPD. SHOW MINIMUM #8 CU.