Plan Review Notes
Plan Review Notes For Permit 20090555
Permit Number 20090555
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-09-22 13:16:09.000001] PERMIT APPLICATION MUST SHOW STATE LICENSE NUMBER
 AND COUNTY REGISTRATION NUMBER.
 2] ON ONE-LINE DIAGRAM, SHOW QUANTITY OF MODULES ON
 EACH STRING
 3] ON ONE-LINE DIAGRAM, SHOW ACTUAL AC SYSTEM OUTPUT
 CURRENT ON COMBINER LABEL & PV DISCONNECT LABEL.
 CURRENT OUTPUT OF PROPOSED SYSTEM IS NOT 60 AMPS
 4] ON ONE-LINE DIAGRAM, ELIMINATE #10 GREEN EGC BETWEEN
 PV DISCONNECT AND SUPPLY SIDE TAP. PV DISCONNECT IS
 BONDED BY GROUNDED CIRCUIT CONDUCTOR, #8 CU MINIMUM.
  