2020-09-15 08:52:09.00000KERRY BARNETT FIRE SAFETY CONSULTING, LLC
 43951 CR 54E, KATHLEEN, FL 33849
  
 FIRE SAFETY INSPECTOR & PLANS EXAMINER CELL (813)
 778-4981
 KERRY BARNETT E-MAIL:
 KBARNETT@FIRESAFETYCONS.COM
 ________________________________________
 PLAN REVIEW #: 20-074 CONTRACTOR: MID STATE FIRE
 EQUIPMENT
 PROJECT: HOOD SUPPRESSION – PAPA JOHNS CONTACT:
 CHRISTOPHER BEACH
 LOCATION: 119 US 27 S TELEPHONE: 863-465-2569
 ADDRESS OF JOB: LAKE PLACID, FL
 PAGES: PACKET
  
 SEPTEMBER 14, 2020
  
 I HAVE RECEIVED AND REVIEWED THE PLANS SUBMITTED FOR
 THE RESTAURANT FIRE SUPPRESSION SYSTEM (ANSUL R102) FOR
 A KITCHEN EXHAUST HOOD SYSTEM/PIZZA OVEN AT PAPA JOHN’S
 PIZZA TO ENSURE COMPLIANCE WITH THE FLORIDA FIRE
 PREVENTION CODE, NFPA 17A, ANY OTHER APPLICABLE CODES,
 STANDARDS, RULES, AND STATUTES. PLANS WERE REVIEWED TO
 THE BEST OF THIS OF THIS PERSON’S ABILITY. COMMENTS
 CONCERNING THIS REVIEW ARE NOTED BELOW. AT THIS TIME,
 PLANS ARE ALLOWED TO MOVE FORWARD. BY PAYING FOR
 PERMIT, CONTRACTOR ACKNOWLEDGES TO AGREE WITH THE
 COMMENTS LISTED. SHOULD ANYONE FEEL COMMENTS ARE NOT
 ENFORCEABLE, HE OR SHE SHALL CONTACT THIS AUTHORITY TO
 RESOLVE BEFORE PERMIT IS ISSUED.
  
 1. ENSURE SYSTEM IS INSTALLED IN ACCORDANCE TO CURRENT
 EDITION OF 17A AND INSTALLATION MANUAL.
 2. ENSURE ELECTRIC SHUTS DOWN UNDER HOOD.
 3. INSTALL A HORN, BELL, STROBE, OR COMBINATION OF ANY
 MENTION THAT WILL GO OFF WHEN SYSTEM ACTIVATES, THUS
 NOTIFYING OCCUPANT(S).
 4. ENSURE THE LENGTH OF THE MANUAL CABLE PULL DOES NOT
 EXCEED 14 INCHES AND PULL IS LOCATED WITHIN 10 FEET
 (MINIMUM IF POSSIBLE) FROM THE PROTECTED APPLIANCES AND
 WITHIN THE PATH OF EGRESS.
 5. ENSURE SYSTEM IS INSTALLED TO ALLOW MAKEUP AIR TO
 SHUT DOWN AND EXHAUST FAN TO REMAIN ON.
 6. ENSURE A K CLASS FIRE EXTINGUISHER IS LOCATED IN
 SPACE. EXTINGUISHER SHALL HAVE A PLACARD INDICATING
 THAT IT IS A SECONDARY BACKUP TO THE AUTOMATIC
 EXTINGUISHING SYSTEM.
 7. ENSURE PULL STATION HAS APPROPRIATE PLACARD
 INDICATING USE.
  
 INSPECTIONS REQUIRED:
  
 1. ACCEPTANCE TEST
  
  
 KERRY BARNETT
  