 PLAN REVIEW #: 20-071 REVIEW FOR: PARKERAIRE
 PROJECT: PAPA JOHNS (HOOD/DUCT) CONTACT: DAVID PAKER
 LOCATION: LAKE PLACID, FL TELEPHONE: 239-997-2665
 ADDRESS OF JOB: 121 US HWY 27
 PAGES: 12
  
 SEPTEMBER 11, 2020
  
  
 I HAVE RECEIVED AND REVIEWED THE PLANS (CAPTIVE AIRE)
 FOR A COMMERCIAL GREASE HOOD/DUCT FOR A PAPA JOHNS AT
 ADDRESS ABOVE. PLANS WERE REVIEWED TO THE BEST OF THIS
 REVIEWER’S ABILITY TO ENSURE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, NFPA 96, AND ANY OTHER
 APPLICABLE CODES, STANDARDS, RULES, AND STATUTES.
 COMMENTS ARE LISTED BELOW. AT THIS TIME, THE PLANS ARE
 NOT APPROVED. ADDITIONAL INFORMATION SHALL BE SUBMITTED
 BASED ON THE COMMENTS BELOW. SHOULD ANYONE HAVE ANY
 QUESTIONS, THIS AUTHORITY MAY BE CONTACTED VIA
 TELEPHONE OR EMAIL NOTED ABOVE.
  
 1. A SCALED DRAWING/PLAN SHALL BE SUBMITTED SHOWING THE
 INSTALLATION OF THE HOOD AND DUCT FOR THIS PROJECT. AN
 ELEVATION DRAWING SHALL BE INCLUDED NOTING HOW THE DUCT
 ROUTES FROM THE HOOD TO THE FAN. ACCESS DOORS SHALL BE
 INDICATED AS WELL. THIS IS NEEDED TO DETERMINE DISTANCE
 FROM COMBUSTIBLES TO DETERMINE OF ANY ADDITIONAL FIRE
 PROTECTION IS REQUIRED EITHER BY FIRE WRAP OF USE OF
 DOUBLE WALL DUCT. IT IS IMPORTANT TO NOTE THE
 CONSTRUCTION TYPE MATERIAL (LIMITED COMBUSTIBLE,
 NON-COMBUSTIBLE, COMBUSTIBLE) THAT THE DUCT AND HOOD
 WILL INSTALLED WITHIN.
 2. A SCALED DRAWING/PLAN SHALL ALSO SHOW ROOF LAYOUT TO
 ENSURE SETBACKS ARE MET FROM EXHAUST TO ANY AIR INLET.
 3. ENSURE APPLIANCES ARE INSTALLED UNDER THE HOOD ARE
 IN ACCORDANCE TO THE HOOD PLACARDS.
 4. ENSURE ROOF TOP FAN SHALL BE HINGED AND HAVE A
 GREASE CUP. ENSURE THERE IS ENOUGH SLACK IN THE
 ELECTRICAL CONNECTION TO ALLOW THE FAN TO BE TIPPED
 WHEN HOOD/DUCT IS BEING CLEANED.
 5. ENSURE HOOD FANS ARE PROPERLY WIRED SO EXHAUST FANS
 REMAIN ON WHEN SYSTEM IS ACTIVATED AND MAKE UP AIR
 SHUTS DOWN.
 6. IF A FIRE WRAP IS TO BE USED, SUCH AS FIRE MASTER
 FAST WRAP” PROVIDE SPEC SHEETS ON WRAP.
 7. ENSURE ACCESS PANEL HAS REQUIRED LISTED GASKET.
 PROVIDE SPEC SHEET OF ACCESS PANEL.
 8. ENSURE THE FAN MEETS THE REQUIRED 10 FT HORIZONTAL
 DISTANCE FROM ANY OTHER AIR INLET
 9. THE FAN CURB SHALL BE A MINIMUM OF 18 INCHES ABOVE
 ROOF TOP WITH TOP OF FAN BEING A MINIMUM OF 40 INCHES
 ABOVE THE ROOF TOP.
  
 INSPECTIONS REQUIRED:
  
 1. LIGHT TEST
 2. TEST & BALANCE (COPY OF REPORT TO BE GIVEN TO THIS
 AUTHORITY AT FINAL INSPECT)
 3. FINAL – CAN BE COMPLETED AT TIME OF SUPPRESSION
 FINAL. APPLIANCES SHALL BE IN PLACE.
  