2020-07-08 15:09:52.00000CONDITIONAL APPROVAL REQUIRES COMPLIANCE WITH NOTE ON
 RISER DIAGRAM: USE 60A FUSES IN PV DISCONNECT. 37
 INVERTERS @ 1.21 - 1.26A, PLUS 25% CONTINUOUS LOAD
 FACTOR REQUIRES 60A OCPD.