Date Text
2020-06-11 08:46:33.00000SHEET PV-4.0, CONDUIT/CONDUCTOR SCHEDULE ITEMS #5, 6, &
 7: EQUIPMENT GROUNDING CONDUCTOR MUST BE MINIMUM #6 AWG
 COPPER (OVERCURRENT PROTECTION GREATER THAN 100A AND
 NOT EXCEEDING 200A).