2020-06-17 15:23:58.00000KERRY BARNETT FIRE SAFETY CONSULTING, LLC
 43951 CR 54E, KATHLEEN, FL 33849
  
 FIRE SAFETY INSPECTOR & PLANS EXAMINER CELL (813)
 778-4981
 KERRY BARNETT E-MAIL:
 KBARNETT@FIRESAFETYCONS.COM
 ________________________________________
 PLAN REVIEW #: 20-042 CONTRACTOR: CARSON CONSULTING,
 LLC
 PROJECT: SHIELD MEDICAL OFFICES CONTACT: N/A
 LOCATION: 6676 US HWY 27 N TELEPHONE: 863-679-2667
 ADDRESS OF JOB: SEBRING, FL ENGINEER: ROBERT HAUG
 PAGES: 20 TELEPHONE: 863-687-4225
  
 JUNE 17, 2020
  
 I HAVE RECEIVED AND REVIEWED THE PLANS FOR A BUSINESS
 OCCUPANCY DEDICATED FOR USE AS MEDICAL OFFICES. PLANS
 WERE REVIEWED TO THE BEST OF THIS REVIEWER’S ABILITY TO
 ENSURE COMPLIANCE WITH THE FLORIDA FIRE PREVENTION
 CODE, FLORIDA STATUTE, FLORIDA ADMINISTRATIVE RULE, AND
 ANY REFERENCE NFPA CODE OR STANDARD, AS WELL AS, ANY
 APPLICABLE LOCAL RULE WITHIN THE COUNTY. AT THIS TIME
 PLANS ARE NOT APPROVED, AND REVISIONS WILL BE REQUIRED.
 IN SUBMITTING REVISIONS, ENSURE A LETTER IS PROVIDED
 RESPONDING TO THE CHANGES AND THE CHANGES WITHIN THE
 PLANS ARE CLOUDED. COMMENTS ASSOCIATED WITH THE REVIEW
 ARE NOTED BELOW. SHOULD ANYONE BELIEVE COMMENTS MADE
 ARE NOT REQUIRED, DOCUMENTATION SHALL BE SUBMITTED
 ALLOWING THE EXEMPTION. ANY QUESTIONS, THIS AUTHORITY
 MAY BE CONTACTED THROUGH ABOVE EMAIL OR TELEPHONE
 NUMBER.
  
 1. PLANS SHALL BE STAMPED/SEAL BY ENGINEER.
 2. SAFEGUARDS FOR CONSTRUCTION SHALL BE IN PLACE IN
 ACCORDANCE WITH NFPA 1 AND NFPA 241, STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS. ENSURE CERTIFIED FIRE EXTINGUISHERS ARE
 PROPERLY LOCATED THROUGHOUT BUILDING DURING
 CONSTRUCTION AND NO SMOKING TAKES PLACE INSIDE THE
 BUILDING. NFPA 1: 16.1.1
 3. ON COVER PAGE IN DESIGN CRITERIA TABLE CORRECT THE
 EDITIONS FOR THE FOLLOWING AND ENSURE PLANS MEET THESE
 REQUIREMENTS.
 - FFPC – 6TH EDITION
 - NFPA 1 – 2015 EDITION W/FLORIDA AMENDMENTS
 - NFPA 101 – 2015 EDITION W/FLORIDA AMENDMENTS
 - NFPA 70 – 2014 EDITION
 4. PLANS INDICATE 1 1 HOUR RATED CORRIDOR, HOWEVER,
 WALL TYPE “A” (LSP) IS NOT SHOWN TO BE A RATED WALL
 WITH CORRIDORS 1 AND 2. FURTHER, THE FLOOR PLAN PAGE
 (A1) DOES NOT INDICATE ANY RATING OR RATED DOORS, ETC…
 NFPA 101:38.3.6.1 REQUIRES A 1 HOUR RATED CORRIDOR.
 THIS BUILDING DOES NOT HAVE AN OPEN FLOOR PLAN, IS NOT
 A SINGLE TENANT BUILDING, AND DOES NOT HAVE A FIRE
 SPRINKLER SYSTEM. PROVIDE A 1 HOUR RATED CORRIDOR WITH
 A UL NUMBER AND DETAILS OF THE WALL AND THE UL NUMBER.
 5. OPENINGS WITHIN THE RATED CORRIDOR SHALL BE
 PROTECTED IN ACCORDANCE WITH 38.3.6.2 AND TABLE 8.3.4.2
 OF NFPA 101.ENSURE ALL HARDWARE FOR RATED DOORS IS
 INDICATED IN THE HARDWARE AND DOOR SCHEDULES ON A1
 6. PROVIDE UL LISTINGS AND DETAIL OF M.E.P.
 PENETRATIONS THAT WILL BE WITHIN THE 1 HOUR CORRIDOR.
 7. THE ATTIC IS REQUIRED TO HAVE DRAFT STOPPING EVERY
 300 SQUARE FEET BASED ON NFPA 101:8.6.11.1. IT APPEARS
 IT IS UNOCCUPIED AND DOES NOT MEET THE FLAME SPREAD
 INDEX REQUIREMENT. SHOW DRAFT STOPPING BASED ON
 8.6.11.3
 8. SHOW ATTIC STORAGE ROOM IN THE PLANS (FLOOR PLAN
 LAYOUT) AND ANY MEP’S THAT WILL BE LOCATED IN THIS
 ROOM.
 9. INDICATE USE OF ATTIC STORAGE AREA. IF THIS IS USED
 FOR MECHANICAL EQUIPMENT AND STORAGE OF RELATED PRODUCT
 FOR THE MECHANICAL, IT CAN BE CONSTRUCTED AS SUCH.
 HOWEVER, IF THIS IS USED FOR GENERAL STORAGE, THE ROOM
 WILL BE REQUIRED TO BE FIRE RATED BASED ON NFPA
 101:38.3.2.1 AND 8.7. IF MECHANICAL ONLY, APPROPRIATE
 SIGNAGE SHALL BE PLACED INDICATING THIS IS A NO STORAGE
 ZONE.
 10. THE REQUIRED 2ND EXIT IS THROUGH THE BREAK ROOM
 (124) IS AN ISSUE. NFPA 101:7.5.2.1 STATES AN EXIT IS
 NOT ALLOWED IN A KITCHEN. THOUGH BY DEFINITION, THE
 BREAK ROOM IS NOT A KITCHEN, IT BECOMES AN OBSTRUCTION
 OF EGRESS. THIS ROOM TYPICALLY HOUSES TABLES/CHAIRS FOR
 THE EMPLOYEES AND MISCELLANEOUS STORAGE. IT IS
 RECOMMENDED TO CHANGE THE EXIT TO THE END OF THE
 CORRIDOR (WHERE WINDOW IS LOCATED) JUST OUTSIDE THE
 BREAK ROOM. IF EXIT IS TO STAY, THERE CAN BE NO
 TABLES/CHAIRS LOCATED IN THIS ROOM AT ANY TIME.
 11. EXIT DOORS MENTION KEY CARD ACCESS. ENSURE THAT
 THIS IS ONLY FOR ACCESS AND NOT ON THE EGRESS SIDE. IS
 SO, IT SHALL COMPLY WITH NFPA 101: CHAPTER 7.
 12. WALL TYPE “C” IS INDICATED AT UTILITY ROOM (122)
 BUT NO DETAIL PROVIDED.
 13. ELECTRICAL PANEL IS IN UTILITY ROOM (122). NO
 STORAGE MAY BE LOCATED WITHIN 36 INCHES OF THE PANEL.
 STRIPE THIS AREA WITH YELLOW DIAGONAL LINES TO INDICATE
 A NO STORAGE ZONE.
 14. INSTALL EMERGENCY LIGHTING IN ACTIVITY ROOM (126),
 ATTIC STORAGE ROOM, AND BREAK ROOM (124). THERE IS
 CURRENTLY AN EXIT/EMERGENCY LIGHT IN THE BREAK ROOM
 ABOVE EGRESS DOOR, HOWEVER DOOR MAY BE RELOCATED BASED
 ON COMMENT #8 ABOVE.
 15. LSP INDICATES A FIRE ALARM SYSTEM. THIS IS NOT A
 REQUIREMENT BY CODE, HOWEVER, IF BEING INSTALLED IT
 SHALL BE PART OF THE PLANS BASED ON RULE 61G15-32.008.
 IF NOT PART OF THE PROJECT, REMOVE FROM PLANS.
 16. INSTALL LIGHTWEIGHT TRUSS SIGN AT ENTRANCE OF
 BUILDING IN ACCORDANCE WITH F.S. 633.027
 17. ENSURE ADDRESS IS LOCATED AT MAIN ENTRANCE MINIMUM
 6 INCHES IN HEIGHT.
 18. INSTALL KNOX BOX NEAR MAIN ENTRANCE AT A MAXIMUM
 HEIGHT OF 6 FT IF INSTALLING FIRE ALARM. APPLY FOR THE
 KNOX BOX AT WWW.KNOXBOX.COM
 19. PROVIDE LOCATION IN PLANS WHERE AHU’S ARE LOCATED.
 20. ALL ROOMS SHALL BE IDENTIFIED TO THEIR USE WITH
 SIGNAGE. SIGNAGE SHALL BE POSTED ON WALL ADJACENT TO
 ROOM. LETTERING SHALL BE MINIMUM 1INCH IN HEIGHT ON
 CONTRASTING BACKGROUND. THIS ASSISTS FD DURING A FIRE
 EMERGENCY IDENTIFYING AREAS OF CONCERN DURING A SEARCH.
 NFPA 101:4.6.1.2
 21. TWO WAY RADIO COMMUNICATION ENHANCEMENT SYSTEM IS
 REQUIRED (NFPA1:11.10.1). THIS IS TO ENSURE SIGNAL
 STRENGTH FOR FD COMMUNICATIONS CAN BE MAINTAINED DURING
 AN EMERGENCY. THIS IS DETERMINED BY THE LOCAL AHJ.
 CONTACT HIGHLANDS COUNTY FM FOR PROCESS.
 22. AN ADDITIONAL FIRE EXTINGUISHER APPEARS TO BE
 NEEDED IN THE CORRIDOR BY DOCTORS OFFICE (116). TRAVEL
 DISTANCE IS GREATER THAN 75 FT.
  
  
  
 KERRY BARNETT
 ___________________________________
 KERRY BARNETT, FIRE SAFETY INSPECTOR & PLANS EXAMINER
 *3RD PARTY REVIEWER FOR HIGHLANDS COUNTY AS ALLOWED PER
 F.S.633
  
  
 ***PLEASE BE ADVISED THIS REVIEW OF PLANS SUBMITTED IS
 A CURSORY REVIEW TO ASSIST THE CONTRACTOR IN COMPLIANCE
 WITH APPLICABLE FIRE SAFETY CODES. THIS REVIEW IS NOT
 INTENDED TO BE A FINAL APPROVAL OF THE SUBMITTED PLANS.
 IT IS THE CONTRACTOR’S SOLE RESPONSIBILITY TO ENSURE
 THAT THE PLANS ARE IN COMPLETE COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES STATE STATUTES AND LOCAL
 ORDINANCES. IN THE EVENT THAT FURTHER EXAMINATION OR
 SITE INSPECTION REVEALS AREAS OF NON-COMPLIANCE, IT
 SHALL BE THE CONTRACTOR’S SOLE RESPONSIBILITY, AT THEIR
 SOLE EXPENSE TO BRING THOSE AREAS IN COMPLIANCE. KERRY
 BARNETT FIRE SAFETY CONSULTING ASSUMES NO
 RESPONSIBILITY FOR THE CONTRACTOR’S FAILURE TO BE IN
 COMPLIANCE WITH ALL APPLICABLE NFPA CODES, STATE
 STATUTES AND LOCAL ORDINANCES.
  