2020-06-18 11:59:32.00000I HAVE REVIEWED THE PLANS FOR PERMIT 20050365, HC ROAD
 AND BRIDGE AVON PARK BARN ADDITION, FOR COMPLIANCE WITH
 THE FLORIDA FIRE PREVENTION CODE (FFPC), SIXTH EDITION.
 THE FOLLOWING NEEDS TO BE ADDRESSED:
 1. SHOW COMBINATION EXIT SIGN/EMERGENCY LIGHTING UNIT
 AT MAN DOOR FROM BUILDING,
 2. SHOW EMERGENCY LIGHTING UNIT IN AREA OF CENTER OF
 BUILDING TO 2/3 WAY BETWEEN MAN DOOR AND ROLL-UP DOOR,
 3. SHOW FIRE EXTINGUISHER ON WALL MOUNT AT MAN DOOR,
 MINIMUM RATING 2A 10B C,
 4. INCLUDE ELECTRICAL PLAN SHEET WITH PLANS.
  
 PLANS ARE APPROVED TO COMMENCE CONSTRUCTION WITH
 COMMENTS INDICATED. REVISED PLANS TO BE SUBMITTED PRIOR
 TO FINAL CO.
  