Plan Review Notes For Permit 20030637
Permit Number 20030637
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-03-27 15:53:45.000001] PLEASE CLARIFY ALL CONDUCTORS AS COPPER OR ALUMINUM
 2] SPECIFY FUSE SIZE IN SERVICE DISCONNECT
 3] CONDUCTORS SUPPLYING CHARGERS MUST HAVE AN
 INSULATION TYPE SUITABLE FOR WET LOCATIONS (THWN, XHHW,
 ETC.)
 4] GROUNDING ELECTRODE SYSTEM MUST SPECIFY AT LEAST TWO
 GROUND RODS MINIMUM SIX FEET APART. SHOW BOTH THE
 SERVICE AND THE TRANSFORMER CONNECTED TO THIS SYSTEM.
 5] SHOW EQUIPMENT GROUNDING CONDUCTOR SIZE FROM SERVICE
 DISCONNECT TO 150KVA TRANSFORMER. IT IS ASSUMED THAT
 ONLY THREE CURRENT-CARRYING CONDUCTOR SETS WILL BE
 INSTALLED ALONG WITH A SET OF EQUIPMENT GROUNDING
 CONDUCTORS.
 6] PERMIT APPLICATION INDICATES A 400 AMP SERVICE. IF
 600 AMP, PLEASE REVISE APPLICATION. (SIZE BASED ON
 SERVICE OVERCURRENT PROTECTION).