Plan Review Notes For Permit 20030428
Permit Number 20030428
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-03-18 11:18:08.000001] ROOF LAYOUT DOES NOT PROVIDE ADEQUATE DETAIL TO
 VERIFY SEPARATION BETWEEN MODULES & ROOF RIDGE.
 MAINTAIN MINIMUM THREE FOOT SEPARATION FROM RIDGE PER
 FL FIRE PREVENTION CODE 11.12.2.2.2.2
 2] RISER DIAGRAM PAGE HEADING INDICATES A TOTAL OF 24
 MODULES; INDIVIDUAL STRING DRAWING INDICATES 14 MODULES
 PER STRING (TOTAL OF 28). RISER DIAGRAM IS APPROVED AS
 DRAWN PROVIDED THAT NO MORE THAN 12 MODULES PER STRING
 ARE INSTALLED.