Plan Review Notes
Plan Review Notes For Permit 20030253
Permit Number 20030253
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2020-03-11 15:36:22.00000SHEETS C-1 AND S-1 ARRAY LAYOUT SHOWS MODULES TOO CLOSE
 TO ROOF RIDGE AND TOO CLOSE TO VALLEYS OR HIPS. A
 MINIMUM SEPARATION OF THREE FEET FROM THE RIDGE IS
 REQUIRED PER FLORIDA FIRE PREVENTION CODE
 11.12.2.2.2.2.
 A MINIMUM SEPARATION OF 1 1/2 FEET FROM A VALLEY OR HIP
 IS REQUIRED WHEN MODULES ARE PLACED ON BOTH SIDES OF
 THE VALLEY OR HIP, PER FLORIDA FIRE PREVENTION CODE
 11.12.2.2.2.1.3. A MINIMUM THREE FOOT
 WIDE ACCESS PATHWAY SHALL BE PROVIDED FROM THE EAVE TO
 THE RIDGE OF EACH ROOF SLOPE WHERE MODULES ARE LOCATED.
 PLEASE PROVIDE SEALED REVISED DRAWINGS SHOWING THESE
 CORRECTIONS.