Date Text
2020-02-24 16:23:14.00000SHEET C-1 ARRAY LAYOUT SHOWS MODULES TOO CLOSE TO ROOF
 RIDGE. A MINIMUM SEPARATION OF THREE FEET FROM THE
 RIDGE IS REQUIRED PER FLORIDA FIRE PREVENTION CODE
 11.12.2.2.2.2 (CODE TEXT ATTACHED)