Plan Review Notes For Permit 19100637
Permit Number 19100637
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-29 11:29:03.000001/29/20 TWO (2) SET OF REVISED PLANS SUBMITTED FOR
 REVIEW-SENT TO COUNTY FIRE CARRIER ERIC LONGSHORE.
  
2019-11-21 10:51:38.00000 
  
  
 HIGHLANDS COUNTY FIRE RESCUE
 FIRE PREVENTION BUREAU 6850 WEST GEORGE BOULEVARD
 SEBRING, FLORIDA 33870
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: NOVEMBER 21, 2019
  
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND
 NEED THE FOLLOWING ISSUES RESOLVED:
  
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM
 ORDINARY HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF
 ROOM 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  
 IF THERE ARE ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 P A G E | 1
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: NOVEMBER 21, 2019
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND NEED THE
 FOLLOWING ISSUES RESOLVED:
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM ORDINARY
 HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF ROOM
 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
 HIGHLANDS COUNTY FIRE RESCUE
 FIRE PREVENTION BUREAU 6850 WEST GEORGE BOULEVARD
 SEBRING, FLORIDA 33870
 863-385-1112
  
  
  
  
  
  
  
  
  
  
  
  
 MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: NOVEMBER 21, 2019
  
 RE: NEW FIRE/EMS HEADQUARTERS BUILDING, PERMIT 19100637
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND
 NEED THE FOLLOWING ISSUES RESOLVED:
  
 1. THE FIRE SPRINKLERS IN THE WAREHOUSE ARE CALCULATED
 AS LIGHT HAZARD AND SHOULD BE AT A MINIMUM
 ORDINARY HAZARD.
 2. THERE SHOULD BE CO DETECTORS AT ALL OPENINGS TO THE
 WAREHOUSE.
 3. NOT SURE ABOUT THE PURPOSE OF THE SMOKE/FIRE DAMPER
 IN THE MEZZANINE. PLEASE EXPLAIN.
 4. FIRE ALARM SYSTEM SHOULD HAVE TAMPER SWITCHES AT THE
 FIRE SPRINKLER BACKFLOW VALVES.
 5. A BI-DIRECTIONAL EXIT LIGHT IS NEEDED AT THE
 INTERSECTION OF CORRIDOR 130 AND 115, IN FRONT OF
 ROOM 118.
 6. PAGE A301 SHOWS A DIRECTIONAL EXIT LIGHT FROM ROOM
 106 TO CORRIDOR 102 IN THE WRONG DIRECTION.
 7. THE GENERATOR CONTROLLERS NEED TO BE MONITORED BY
 THE FIRE ALARM FOR THE FOLLOWING CONDITIONS:
 • GENERATOR RUNNING.
 • GENERATOR FAULT.
 • GENERATOR SWITCH IN NONAUTOMATIC POSITION.
 8. SEPARATE PERMITS ARE NEEDED FOR:
 • AUTOMATIC FIRE SPRINKLER SYSTEM (BOTH ABOVE GROUND
 AND UNDERGROUND).
 • FIRE ALARM SYSTEM.
 • ACCESS CONTROL SYSTEM.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  