Plan Review Notes For Permit 19100620
Permit Number 19100620
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2019-10-31 15:54:10.00000APPROVED CONDITIONALLY; COMPLIANCE WITH THE FOLLOWING
 NOTES REQUIRED:
 1] METAL RACEWAYS ON LINE SIDE OF PV AC DISCONNECT MUST
 BE BONDED (BONDING BUSHING, ETC)
 2] PANELS MUST MAINTAIN MINIMUM 3 FOOT CLEARANCE BELOW
 ROOF RIDGE IN COMPLIANCE WITH FLORIDA FIRE PREVENTION
 CODE
 3] COMPLY WITH RAPID SHUTDOWN REQUIREMENTS PER NEC
 690.12 AND AFFIX COMPLIANCE LABEL AT PV AC DISCONNECT
 OR INVERTER