Plan Review Notes For Permit 19100611
Permit Number 19100611
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2019-10-28 16:22:41.000001] SHEET PV-1.0: SHOW ROOF LAYOUT COMPLIANT WITH
 FLORIDA FIRE PREVENTION CODE 11.12.2.2.2. PV MODULES
 MUST BE LOCATED NO LESS THAN 3 FT BELOW THE RIDGE; PV
 MODULES SHALL BE LOCATED NO CLOSER THAN 1 1/2 FT TO A
 HIP OR A VALLEY IF MODULES ARE TO BE PLACED ON BOTH
 SIDES OF THE HIP OR VALLEY.
  
 2] SHEET PV-4.0: ELIMINATE #6 THWN GROUNDING CONDUCTOR
 (ITEM "F") BETWEEN EXISTING SERVICE PANEL AND SOLAR
 DISCONNECT. ALTERNATIVELY, SHOW THE #6 NEUTRAL
 CONDUCTOR FROM THE SERVICE AS BEING BONDED TO THE SOLAR
 DISCONNECT ENCLOSURE. THIS PROCEDURE APPLIES ASSUMING A
 SUPPLY-SIDE TAP FOR THE PV SYSTEM, AS INDICATED ON
 DRAWINGS.