Plan Review Notes
Plan Review Notes For Permit 19100606
Permit Number 19100606
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-03-02 15:14:13.00000MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: MARCH 2, 2020
 RE: KOSAN CRISPLANT PROPANE FACILITY, RESUBMITTAL,
 PERMIT# 19100606
 THE FLORIDA FIRE PREVENTION CODE (FFPC) RECOGNIZES TWO
 OPTIONS FOR COMPLIANCE WITH THE GOALS AND OBJECTIVES OF
 THE CODE. THESE COMPLIANCE OPTIONS ARE AS FOLLOWS:
 1. THE PRESCRIPTIVE-BASED OPTION OR,
 2. THE PERFORMANCE-BASED OPTION.
 THESE PLANS DO NOT APPEAR TO FOLLOW THE
 PRESCRIPTIVE-BASED PROVISIONS.
 GIVEN THE COMPLEXITY OF THIS PROJECT, AND THE
 LIKELIHOOD OF A PERFORMANCE-BASED DESIGN, I AM
 REQUIRING THE SUBMITTER OF THESE PLANS TO HAVE THEM
 REVIEWED BY AN INDEPENDENT THIRD PARTY AT THE
 SUBMITTER’S EXPENSE.
 THIS THIRD-PARTY REVIEWER SHALL HAVE EXPERTISE IN FIRE
 PROTECTION ENGINEERING, INDUSTRIAL FACILITIES
 CONDUCTING BULK DISPENSING OF LIQUEFIED PETROLEUM GAS
 INDOORS, ALONG WITH A GOOD WORKING KNOWLEDGE OF THE
 FLORIDA FIRE PREVENTION CODE. THEY MUST HAVE A CURRENT
 P.E. LICENSE AND BE IN GOOD STANDING WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 THE INDEPENDENT REVIEWER SHALL PROVIDE AN EVALUATION OF
 THE SUBMITTALS AND RECOMMEND ANY NECESSARY CHANGES,
 ADDITIONS, OR DELETIONS OF THE PROPOSED DESIGN,
 OPERATION, AND PROCESSES TO MY OFFICE. ONCE THIS IS
 RECEIVED MY OFFICE WILL MAKE THE FINAL DETERMINATION AS
 TO WHETHER THE PROVISIONS OF THE FFPC HAVE BEEN MET.
 FINAL SELECTION OF A THIRD-PARTY REVIEWER WILL NEED
 APPROVAL BY MY OFFICE. (NFPA 1, 1.15)