2019-12-02 11:46:02.00000TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: NOVEMBER 27, 2019
 RE: KOSAN CRISPLANT PROPANE FACILITY, PERMIT# 19100606
 I HAVE REVIEWED THESE PLANS IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, WHICH
 INCLUDES PUBLICATIONS REFERENCED IN NFPA 1, AND 101.
 ALL REFERENCES TO NFPA 1, AND NFPA 101 ARE OF THE
 FLORIDA SPECIFIC EDITIONS.
 IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE
 THIS WOULD BE CONSIDERED A HIGH-HAZARD INDUSTRIAL
 OCCUPANCY (WITH A POSSIBLE STORAGE OCCUPANCY), AND A
 BUSINESS OCCUPANCY SEPARATED WITH A 2-HOUR FIRE
 BARRIER. HOWEVER, IT DOES NOT SPECIFY THE ASSOCIATED
 HAZARDS OR THE CLASSIFICATION OF THE FACILITY REGARDING
 PROPANE. FOR EXAMPLE, IN ACCORDANCE WITH NFPA 58, IS
 THIS CONSIDERED A UTILITY LP-GAS PLANT, BULK PLANT,
 INDUSTRIAL PLANT, DISPENSING STATION, ETC.? THIS
 INFORMATION WILL HELP TO APPROPRIATELY APPLY THE CODE.
 I AM UNABLE TO COMPLETE THE REVIEW DUE TO THE
 FOLLOWING:
 1. NEED TO SPECIFY THE CLASSIFICATION OF THE FACILITY
 AND THE SCOPE OF OPERATION REGARDING PROPANE.
 2. PROVIDE A SITE PLAN. THE SITE PLAN MUST DEMONSTRATE:
 • PROVISIONS FOR FIRE DEPARTMENT ACCESS (NFPA 1,
 SECTION 18.2).
 • AN ADEQUATE FIRE FLOW. THE REQUIRED FIRE FLOW FOR
 THIS PROJECT IS 1750 GPM FOR A DURATION OF 2 HOURS (SEE
 NFPA 1, TABLE 18.4.5.2.1). CURRENTLY THE PLANS SHOW AN
 EXISTING FIRE HYDRANT LOCATED AT 11751 TWITTY RD.
 PROVIDING 520 GPM FLOW AT 60 PSI. THE CODE HAS
 PROVISIONS WHERE THE REQUIRED FLOW RATE CAN POSSIBLY BE
 MODIFIED (SEE NFPA 1, 18.4.3 AND 18.4.5.3). THOSE
 PROVISIONS MAY BE CONSIDERED WHEN PLANS FOR FIRE
 PROTECTION ARE SUBMITTED.
 • LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS.
 INCLUDE FLOW DATA.
 • LOCATIONS, SIZES, AND TYPES OF CONTAINERS. INCLUDE
 PROPERTY LINES, AND IMPORTANT BUILDINGS (NFPA 58,
 CHAPTER 6).
 3. PROVIDE A FIRE PROTECTION PLAN IN ACCORDANCE WITH
 NFPA 58, SECTION 6.27.
 4. PROVIDE DETAILED INFORMATION DEMONSTRATING
 COMPLIANCE WITH NFPA 30 AND 33 FOR THE PAINTING CABIN
 AND THE ASSOCIATED FLAMMABLE LIQUID STORAGE.
 5. PROVIDE SPECIFICATION SHEETS AND INSTALLATION
 DETAILS FOR FIRE DOOR “125”.
 6. EGRESS DOOR “123” NEEDS PANIC HARDWARE.
 7. THE EXIT IN THE RECEIVING ROOM TRAVERSES THE
 BUSINESS OCCUPANCY, THUS MAKING THIS A MIXED OCCUPANCY
 INSTEAD OF A SEPARATED OCCUPANCY. TO REMAIN A SEPARATED
 OCCUPANCY, YOU WILL NEED TO REMOVE THE EXIT SIGN THAT
 LEADS INTO THE BREAKROOM AND PROVIDE AN EXIT WHICH IS
 INDEPENDENT OF THE BUSINESS OCCUPANCY. (NFPA 101,
 SECTION 6.1.14.1.2)
 8. SEPARATE PERMITS WILL BE REQUIRED FOR THE
 INSTALLATION OF ALL APPLICABLE FIRE PROTECTION SYSTEMS
 INCLUDING:
 • FIRE ALARM
 • FLAMMABLE LIQUID STORAGE
 • FLAMMABLE LIQUID SPRAY BOOTH
 • ANY WATER BASED FIRE PROTECTION SYSTEMS.
 9. PROVIDE THE BUILDINGS ELECTRICAL DISCONNECT ON THE
 BUILDING EXTERIOR NEAR THE SERVICE ENTRANCE. (NFPA 1,
 SECTION11.1.7)
 I AM RETAINING ONE COPY OF THE PLANS IN MY OFFICE TO
 ANSWER ANY QUESTIONS THEY MAY HAVE.
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES PRIOR TO
 PERMITTING