2019-09-24 16:49:44.00000RISER DIAGRAM INDICATES "LOAD SIDE TAP ON THE LOAD SIDE
 OF THE MAIN BREAKER"; NO OVERCURRENT PROTECTION IS
 SHOWN IN THE PANEL. PLEASE CLARIFY HOW THIS WILL BE
 ACCOMPLISHED. ARE THE SOLAR INPUT CONDUCTORS CONSIDERED
 A FEEDER TAP?