Plan Review Notes For Permit 19090366
Permit Number 19090366
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-09-20 12:03:48.000001. ENSURE SYSTEM IS INSTALLED IN ACCORDANCE TO CURRENT
 EDITION OF 17A AND INSTALLATION MANUAL.
 2. ENSURE A HORN, BELL, STROBE, OR COMBINATION OF ANY
 MENTION THAT WILL GO OFF WHEN SYSTEM ACTIVATES, THUS
 NOTIFYING OCCUPANT(S).
 3. ENSURE PULL STATION LOCATED IN THE PATH OF EGRESS
 NEAR ENTRANCE TO MIXING ROOM.
 4. ENSURE SYSTEM IS INSTALLED TO ALLOW MAKEUP AIR TO
 SHUT DOWN AND EXHAUST FAN TO REMAIN ON.
 5. ENSURE PULL STATION HAS APPROPRIATE PLACARD
 INDICATING USE.
  
  
  
 INSPECTIONS REQUIRED:
  
 1. ACCEPTANCE TEST
  
 KERRY BARNETT
 __________________________________________________
 KERRY BARNETT, FIRE SAFETY INSPECTOR & PLANS EXAMINER
  
2019-09-19 11:07:18.00000THREE (3) SET OF PLAN SUBMITTED FOR REVIEW BY CITY OF
 AVON PARK FIRE-CARRIER ERIC LONGSHORE.