2019-07-03 12:22:48.00000PER 690.9 (A), THE BACKFED PV INPUT BREAKER IN THE
 SERVICE PANEL ALSO PROVIDES OVERCURRENT PROTECTION FOR
 CONDUCTORS AND CURRENT-LIMITED EQUIPMENT (IN THIS CASE
 THE INVERTER AND THE CONDUCTORS FROM THE SERVICE PANEL
 TO THE INVERTER). CHANGE THIS CIRCUIT BREAKER TO A 30
 AMP, BASED ON USE OF A 5KW INVERTER.