2019-06-28 16:28:08.00000SHEET E-1: CONDUCTORS BETWEEN ENPHASE COMBINER BOX AND
 THE FUSED DISCONNNECT ARE SHOWN AS #10 CU THWN.
 AMPACITY OF THESE CONDUCTORS IS NOT SUFFICIENT FOR 125%
 OF TOTAL PV OUTPUT OF 38 AMPS. SHOW A MINIMUM CONDUCTOR
 SIZE OF #8 THWN CU.