Plan Review Notes For Permit 19060338
Permit Number 19060338
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2019-07-17 16:10:25.00000REVISED RISER DIAGRAM RECEIVED.
  
 1] CONDUCTORS FROM NEW SOLAR COMBINER PANEL TO FUSED
 DISCONNECT AND FROM FUSED DISCONNECT TO SERVICE MUST BE
 INCREASED TO #4 COPPER IF USING 80 AMP FUSES AS SHOWN.
 ALTERNATIVELY, 60 AMP FUSES MAY BE USED IF THESE
 CONDUCTOR SIZES REMAIN AS #6 COPPER (ASSUMING A 5KW
 INVERTER PLUS A 6KW INVERTER USED PER THIS REVISED
 DRAWING).
 REFER TO NEC 690.9(A)
  
 2] REVISE PLAN NOTE UNDER "SYSTEM B" LABEL TO SHOW THAT
 SYSTEM B USES A 5 KW INVERTER. THE EXISTING NOTE
 INDICATES THAT SYSTEM B IS EXACTLY THE SAME AS SYSTEM
 A.
  