Plan Review Notes For Permit 19060088
Permit Number 19060088
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-08-27 12:44:43.00000MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: AUGUST 27, 2019
 RE: FLORIDA HOSPITAL HEARTLAND, 24 BED BUILDOUT AND
 CARDIAC CENTER, 4200 SUN N LAKES BLVD. SEBRING, FLORIDA
 33872
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH EDITION. PLEASE
 HAVE THE APPLICANT ADDRESS THE FOLLOWING COMMENTS:
 1. ON PAGES G110 AND G111 THE ONE HOUR FIRE BARRIER
 SEPARATING SMOKE COMPARTMENT SC-1K AND SC-1L DOES NOT
 COMPLETELY MAKE A FIRE BARRIER. INSTEAD IT ADJOINS A
 ONE HOUR SMOKE WALL.
 2. ON PAGE M112 THERE IS A FIRE DAMPER IN THE SMOKE
 WALL SEPARATING ROOM 1843 CLEAN HOLD FROM THE SHELL. IF
 IT IS FOUND THAT THIS SHOULD ALSO BE A FIRE WALL IN
 ACCORDANCE WITH THE PREVIOUS COMMENT, THEN IT SHOULD BE
 A COMBINATION FIRE/SMOKE DAMPER.
 I AM RETURNING THESE PLANS TO YOUR OFFICE WITH APPROVAL
 TO MOVE FORWARD WITH THE PERMIT PROCESS CONTINGENT ON
 RESOLUTION OF THE ABOVE COMMENTS.