2019-06-06 16:17:19.00000REFERENCE 705.12 (D)(2)(3)(B): 125% OF INVERTER OUTPUT
 PLUS MAIN BREAKER RATING EXCEED 120% OF BUSSBAR RATING
 PER SUBMITTED DRAWINGS.
 CALC: (6000 X 1.25) / 240 = 31.25 AMPS.
 31.25 + 150 MAIN = 181.25 AMPS
 150A BUSS RATING X 1.2 = 180 AMPS.
 USE 200 AMP BUSS RATING WITH 150A MAIN OR USE
 SUPPLY-SIDE TAP FOR PV INPUT.