Plan Review Notes For Permit 19050663
Permit Number 19050663
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2019-08-08 16:27:54.00000PER INSPECTION NOTES 6/24/19, UNGROUNDED CONDUCTORS
 BETWEEN THE POWER COLLECTION PANEL AND THE SUPPLY-SIDE
 CONNECTION SHOULD BE #3 COPPER, NOT #4 COPPER. PV
 OUTPUT CIRCUITS ARE CONSIDERED CONTINUOUS LOADS.
 (7600 + 11400) X 1.25 /240 = 98.96 AMPS.
 REQUEST CONTRACTOR TO PROVIDE FILE ATTACHMENT LETTER OR
 REVISED DRAWING SHOWING CORRECT SIZE CONDUCTORS.