Plan Review Notes For Permit 19050501
Permit Number 19050501
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-19 08:36:20.000004. IS THERE AN ISOLATION VALVE IN THE WATER SYSTEM TO
 THE NORTH OF THE “POINT OF SERVICE” FOR THE FIRE LINE?
 THE PLAN CLEARLY REFLECTS A VALVE TO THE SOUTH.
 5. THE FIRE ALARM SYSTEM SHOULD SUPERVISE THE GENERATOR
 FOR THE FOLLOWING:
 NFPA 101
 9.1.3.2 NEW GENERATOR CONTROLLERS SHALL BE MONITORED BY
 THE FIRE ALARM SYSTEM, WHERE PROVIDED, OR AT AN
 ATTENDED LOCATION, FOR THE FOLLOWING CONDITIONS:
 (1) GENERATOR RUNNING
 (2) GENERATOR FAULT
 (3) GENERATOR SWITCH IN NONAUTOMATIC POSITION
 I AM RETURNING THESE PLANS TO YOUR OFFICE WITHOUT FIRE
 CODE APPROVAL UNTIL ALL COMMENTS HAVE BEEN RESOLVED.
 PLEASE HAVE THE APPLICANT CONTACT ME WITH ANY
 QUESTIONS.
2019-06-19 08:36:12.00000FIRE REVIEW: MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
 DATE: JUNE 18, 2019
 RE: FLORIDA CANCER SPECIALIST PERMIT #19050501
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE 6TH EDITION, AND HAVE THE
 FOLLOWING COMMENTS THAT NEED ADDRESSED:
 1. THE OVERHANG AT THE FRONT ENTRANCE WILL NEED A
 MINIMUM OVERHEAD CLEARANCE OF 12’ FOR COUNTY AMBULANCE
 ACCESS.
 NFPA 1
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13’
 6”.
 18.2.3.4.1.2.1 VERTICAL CLEARANCE SHALL BE PERMITTED TO
 BE REDUCED, PROVIDED SUCH REDUCTION DOES NOT IMPAIR
 ACCESS BY FIRE APPARATUS, AND APPROVED SIGNS ARE
 INSTALLED AND MAINTAINED INDICATING THE ESTABLISHED
 VERTICAL CLEARANCE WHEN APPROVED.
 2. HVAC SMOKE DETECTORS NEED TO BE LOCATED AS FOLLOWS:
 NFPA 90A
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS
 IN AIR SUPPLY SYSTEMS HAVING A CAPACITY GREATER THAN
 2000 FT3/MIN.
 3. HVAC SMOKE DETECTORS NEED TO BE SUPERVISED BY THE
 FIRE ALARM SYSTEM.
 NFPA 90A
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE.
2019-05-23 11:43:28.00000*FOR PLAN REVIEW ONLY