Plan Review Notes For Permit 19050221
Permit Number 19050221
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2019-06-06 14:14:23.00000 
 MEMORANDUM
  
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., BATTALION CHIEF, FIRE
 MARSHAL
  
 DATE: JUNE 6, 2019
  
 RE: VALLEJO AUTOMOTIVE SHOP, PERMIT 19050221, FIRE CODE
 REVIEW.
  
  
  
 THIS PERMIT DRAWING SHOWS A 5,000 FT2 SHELL BUILDING
 WITH TWO RESTROOMS, TWO SMALL OFFICES, SOME
 ELECTRICAL AND LIGHTING, WITH THE REST OF THE BUILDING
 WIDE OPEN. IT IS IDENTIFIED AS AN
 “AUTOMOTIVE SHOP” AND A “SPECIAL PURPOSE INDUSTRIAL
 OCCUPANCY”.
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH
 EDITION, WITH THE FOLLOWING ISSUES NEEDING TO BE
 ADDRESSED:
  
 1. IDENTIFY ALL PROPOSED HAZARDS ALONG WITH REQUIRED
 FIRE PROTECTION. EXAMPLES OF HAZARDS WOULD BE
 FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AND/OR
 DISPENSING; TIRE STORAGE OVER 20,000 CUBIC FEET;
 REPAIRING LNG/CNG-FUELED, LP-GAS-FUELED, OR HYDROGEN-
 FUELED VEHICLES; HOT WORK; PAINT AND BODY
 WORK; ETC. (NFPA 1, CHAPTERS 30, 41, 43).
 2. PROVIDE A LIFE SAFETY PLAN. THE LIFE SAFETY PLAN
 SHOULD INCLUDE AS APPLICABLE: LIGHTING AND
 EMERGENCY LIGHTING (INCLUDING TO A PUBLIC WAY); EXIT
 LIGHTING; TRAVEL DISTANCES, DEAD-ENDS, AND
 COMMON PATH OF TRAVEL, OCCUPANT LOAD; CHANGES IN
 ELEVATION ALONG THE EGRESS PATH; DOOR HARDWARE;
 FIRE RATED SEPARATIONS.
 3. FLOOR DRAINAGE AND SLOPING. (NFPA 1, SECTION30.2.5)
 4. HVAC (NFPA 1, SECTION30.2.9)
  
 ADDRESSING THESE ISSUES MAY SPUR FURTHER FIRE CODE
 REQUIREMENTS. THAT SAID, I WOULD BE WILLING TO
 MEET WITH THE APPLICANT TO HELP THEM STREAMLINE
 COMPLIANCE.
  
 I AM RETURNING THESE DRAWINGS TO YOUR OFFICE WITHOUT
 FIRE CODE APPROVAL.
  