Plan Review Notes
Plan Review Notes For Permit 18070555
Permit Number 18070555
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2019-01-03 11:12:12.00000RECEIVED REVISED ELECTRIC PLANS FROM CONTRACTOR
 01/03/2019
2018-09-25 08:17:55.00000PLAN REVIEW NOTES: ROYAL OAKS TRIPLEX PERMIT # 18070555
  
 I HAVE REVIEWED THE PLANS FOR THIS PROJECT AND THE
 FOLLOWING ITEMS NEED TO BE ADDRESSED FOR RESUBMITTAL OF
 PLANS;
  
 1: A SECONDARY MEANS OF EGRESS WILL HAVE TO BE ADDED TO
 THE “DEN” IN UNIT 2.
 2: COMBINATION SMOKE CO2 DETECTORS WILL HAVE TO BE
 ADDED WITHIN 10’ OF ENTRANCE TO SLEEPING AREAS.
 3: A SERVICE OUTLET WILL HAVE TO BE ADDED WITHIN 25’ OF
 A/C CONDENSING UNITS.
 4: NOTE 6 ON FIREWALL DETAIL STATES “PERIMETER MAY BE
 CAULKED WITH SHEETROCK BRAND ACOUSTICAL SEALANT.”
 PERIMETER WILL HAVE TO BE CAULKED WITH FIRE RATED
 CAULK. REMOVE NOTE 6 AND ADD FIRE CAULK NOTE.
 5: ADD NOTE TO ELECTRICAL PAGE STATING THAT ALL
 ELECTRIC TO MEET NEC 2014. (ARC FAULT PROVISIONS AND
 DISHWASHERS AND WASHING MACHINES GFCI PROTECTED.)
 6: OUTLETS WILL NEED TO BE ADDED IN FRONT BEDROOMS BY
 CLOSETS TO PROVIDE OUTLET WITHIN 6’ OF DOOR ENTRY.
  
 PLEASE MAKE THESE ADDITIONS/CORRECTIONS TO PLANS ALONG
 WITH FIRE COMMENTS AND RESUBMIT PLANS FOR APPROVAL.
  
  