2019-02-18 13:14:12.000002/18/19 THREE (3) SET OF REVISED PLAN SUBMITTED FOR
 REVIEW-CARRIER ERIC LONGSHORE.
2018-08-16 13:13:00.00000MEMORANDUM
  
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
 DATE: AUGUST 16, 2018
 RE: FELLOWSHIP HALL PERMIT #18050783
 I HAVE REVIEWED THESE PLANS FOR COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, SIXTH EDITION,
 AND HAVE FOUND THE FOLLOWING ISSUES:
  
 1. MISSING A SEATING PLAN OR PLANS. EACH PROPOSED
 SEATING ARRANGEMENT WILL NEED TO CONFORM TO
 SECTION 12.7.9 OF THE LIFE SAFETY CODE.
 2. THE PLANS DO NOT SHOW ANY DETAILS OF THE EXIT
 DISCHARGE TO A PUBLIC WAY. THE EXIT DISCHARGE
 WILL NEED TO CONFORM TO THE REQUIREMENTS OF SECTIONS
 7.7 AND 7.9 OF THE LIFE SAFETY CODE AND
 PROVIDE DRAWINGS OF ANY DIFFERENCES IN ELEVATIONS OUT
 TO A PUBLIC WAY.
 3. DRAFT STOPPING IS REQUIRED EVERY 3,000 FT2 PER
 SECTION 8.6.11 OF THE LIFE SAFETY CODE.
 4. THE PLANS SHOW A KITCHEN STOVE. THIS WILL NEED TO
 MEET THE REQUIREMENTS OF NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS,
 2014 EDITION.
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  