-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 18040933
Permit Number 18040933
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-07-30 09:28:23.000007/30/18 REVISON SUBMITTED (TWO SET CONTAINING ONE PAGE
 FOR EACH PERMIT)- CARRIER ERIC LONGSHORE.
2018-06-20 10:37:52.00000TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
 DATE: JUNE 20, 2018
 RE: WILLIE DOWNS VILLAS PERMIT # 18040933; 18040937;
 18040940; 18040953; 18040954
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND NEED THE
 FOLLOWING ISSUES RESOLVED:
 1. THE FOLLOWING BUILDINGS ARE REQUIRED TO HAVE A
 SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM:
  18040933
  18040937
  18040940
  18040953
 (SEE LIFE SAFETY CODE 30.3.5)
 2. HVAC IS BLOCKING ESCAPE WINDOWS IN THE FOLLOWING
 BUILDINGS:
  18040937
  18040940
  18040953
 (SEE LIFE SAFETY CODE 30.2.1.2)
 3. PROVIDE LIGHTING, EMERGENCY LIGHTING, AND
 ILLUMINATED EXIT SIGNS TO A PUBLIC WAY IN BUILDING
 18040954. (SEE LIFE SAFETY CODE 12.2.8; 12.2.9;
 12.2.10)
 4. THE KITCHEN IN BUILDING 18040954 DOES NOT SHOW
 COOKING FACILITIES. IF THE APPLICANT DECIDES TO ADD
 COOKING EQUIPMENT, THEN SEPARATE PERMITS WOULD BE
 NECESSARY.
 ALL REFERENCES TO THE LIFE SAFETY CODE ARE FOR THE
 FLORIDA SPECIFIC EDITION.
 PLEASE
2018-04-26 10:01:06.00000TWO (2) SET OF PLAN SENT TO COUNTY FIRE FOR REVIEW
 CARRIER ERIC LONGSHORE.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved