2018-02-14 15:27:23.00000MEMORANDUM
 TO: ERIC LONGSHORE, BUILDING OFFICIAL
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
 DATE: FEBRUARY 14, 2018
 RE: TREND SHOP, PROJECT #17121259
 THESE PLANS DESCRIBE THE CONSTRUCTION OF A CLASS B
 MERCANTILE OCCUPANCY THAT IS APPROXIMATELY 6,816 FT2. I
 HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE 5TH EDITION, AND HAVE
 FOUND THE FOLLOWING ISSUES:
 1. THERE IS A COMBINATION EMERGENCY AND EXIT LIGHT THAT
 IS NOT OVER AN EXIT ON THE REAR WALL.
 2. THE LIFE SAFETY PLAN DOES NOT SHOW AN ACTUAL FLOOR
 PLAN WITH ALL THE NECESSARY INFORMATION. THEY WILL NEED
 TO DESIGN THE EGRESS SYSTEM IN ACCORDANCE WITH THE LIFE
 SAFETY CODE, CHAPTER 36 AND ADDRESS THE FOLLOWING
 INFORMATION:
  ISLE WIDTHS
  TRAVEL DISTANCE
  COMMON PATH OF TRAVEL
  DEAD-END CORRIDORS
  EGRESS DOOR HARDWARE
  LIGHTING, EMERGENCY LIGHTING, AND EXIT
 LIGHTING
 3. THE REAR EXIT IS THROUGH A STORE ROOM. THIS IS NOT
 ALLOWED UNLESS THE BUILDING HAS AN AUTOMATIC FIRE
 SPRINKLER SYSTEM. (LSC 36.2.5.11)
 4. THE PLANS DESCRIBE DRAFTSTOPPING FOR “SINGLE FAMILY
 DWELLINGS”. PLEASE SHOW A DRAFTSTOPPING PLAN THAT IS IN
 ACCORDANCE WITH SECTION 8.6.11 OF THE LIFE SAFETY CODE.
 THIS SHOULD INCLUDE:
  LOCATIONS
  MATERIALS
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES.
  